Siemens S7-1200 vs. S7-1200 G2: Comparison and Upgrade Guide

Industrial controllers, like most modern electronics, continue to improve, getting faster, smaller, and more capable, and the Siemens SIMATIC S7-1200 is no exception. The S7-1200 G2 is the successor to the original S7-1200, but upgrading isn’t necessarily a one-to-one hardware replacement. It fills the same low-cost, high-function role while offering increased memory and processing performance in a smaller footprint.

What Is the S7-1200 G2?

The S7-1200 G2 is the second generation of S7-1200 processors, a low-cost compact industrial controller with built-in IO. For space-conscious applications or small channel-count machines, the built-in IO provides a high-value solution, while additional IO cards and remote IO capabilities still allow it to expand to larger applications. It’s not a direct replacement in all features for the S7-1200 and is not reverse-compatible with S7-1200 PLC IO cards, but it does work with existing remote IO and drives.

How Does it Compare with the S7-1200?

Currently, there are only two broad models of S7-1200 G2: the S7-1212 G2 and S7-1214 G2. Both come with AC and DC power input options as well as DC or Relay outputs options, just like the first-gen S7-1200. Additionally, both offer a failsafe option for safety applications. Compared with the original S7-1212 and S7-1214, the only direct downgrade is the lack of analog input channels, which can easily be resolved by adding an SB 1233 analog input signal board (6ES7233-4HD50-0XB0).

S7-1200

CPUIOProgram and Working MemoryRetentivity
12116DI/4DO/2AI
12128DI/6DO/2AI100kB10kB
121414DI/10DO/2AI150kB10kB
121514DI/10DO/2AI/2AO200kB10kB
121714DI/10DO/2AI/2AO250kB10kB

S7-1200 G2

CPUIOProgram MemoryWorking MemoryRetentivity
1212 G28DI/6DO150kB500kB20kB
1214 G214DI/10DO100kB750kB20kB

S7-1200 G2 Limitations

With firmware update V4.1, there are very few features from the S7-1200 that the S7-1200 G2 does not currently support, including:

  • Non-optimized blocks
  • Enable outputs in stop
  • AS-I Control

There are also some features, like teleservice, that the S7-1200 G2 has replaced with more modern web services and other methods.

When to Select the S7-1200 G2 vs the S7-1200 (vs S7-1500)

Beyond the above-listed features, the S7-1200 G2 can handle much more than the original S7-1200 and can be treated as a drop-in replacement. If your application needs one or more of the features listed, there are some workarounds as well as the S7-1500 series.

Hardware selection flowchart for upgrading legacy Siemens SIMATIC S7-1200 (G1) controllers to the newer SIMATIC S7-1200 G2 generation.

Upgrading from the S7-1200 to S7-1200 G2

To convert to an S7-1200 G2, you will need TIA Portal version 20 or higher. First, add an S7-1200 G2 controller to your existing project. Then copy over PLC Data Types, External source files, PLC tags, program blocks, and Technology objects. You can also copy over watch and force tables, as well as traces, or recreate them on the new controller.

Devices & networks editor in Network view inside Siemens TIA Portal.

When copying over PLC tags, make sure that the address and physical mapping match between the original PLC and the new PLC. Pay particular attention to analog inputs and outputs that will need to be moved to IO cards, as the built-in analog channels start at %IW64 and external analog cards tend to start at %IW96.

hardware and I/O configuration in Siemens TIA Portal for a SIMATIC S7-1214C DC/DC/DC PLC.
TIA Portal configuration screen featuring a Siemens SIMATIC S7-1200 G2 CPU 1214C DC/DC/DC PLC.

Motion control and technology objects have changed slightly in the new S7-1200 G2 and must be manually converted and adapted. In general, the motion capabilities have been significantly expanded, giving you even more available options.

Finally, compile the new PLC and check for any errors or missing blocks.

Key Takeaways

The Siemens S7-1200 G2 offers operators a compelling upgrade path for users seeking greater performance, more memory, and a smaller footprint that can more easily fit into existing installations, while maintaining compatibility with many existing systems and workflows. Although there are a few feature differences and some migration steps to consider, the enhanced capabilities and expanded options make the S7-1200 G2 a strong choice for modern industrial automation projects.

By carefully following the recommended upgrade procedures, users can take full advantage of the improvements and future-proof their control systems for years to come.