Blog

WinCC Comfort/Advanced V13 SP1: Pop-Up Screens and Slide-In Screens

WinCC Comfort/Advanced V13 SP1: Pop-Up Screens and Slide-In Screens

Earlier this year (January 2015), Siemens released their latest service pack for the TIA Portal V13. This included updates to Step7 V13 SP1 and WinCC Comfort/Advanced V13 SP1, along with several others. Along with the WinCC V13 SP1 pack came the addition of the Pop-Up Screen and Slide-In Screen features. It is important to note that this is only available for HMIs running WinCC Comfort/Advanced V13 SP1 and WinCC Runtime Advanced V13 SP1. Currently, these features are only available for Comfort and Mobile Panels as well as PCs running Runtime Advanced.

Relevant Downloads:

Let’s get into some of the details.

Pop-Up Screens

The configuration of Pop-Up Screens and Slide-In screens can be accessed in the Project Tree under the Screen Management section.

Project Tree in Screen Management Section

Pop-ups essentially function as global faceplates. This pop-up can be called from any screen and will be placed at the configured location on the screen. The main difference between faceplates and pop-ups is that pop-ups do not have their own interface or properties. This means that you cannot pass information to the pop-up when it is called, and instead need to rely on multiplexed tags and scripting in order to achieve dynamic functionality.

Below is a picture of the pop-up screen editing window and an example of a VFD motor control pop-up.

Pop-up screen editing window

Notice that it is very similar to the regular screen editing interface. The only difference is that the size of the pop-up can be configured. This is easily done via the Properties menu.

Pop-up screen properties menu

Once you have created your pop-up, you can then call your pop-up on any screen by using the system event “ShowPopupScreen”.

System event "ShowPopupScreen"

This event can display your pop-up at the configured coordinates on any screen.

Popup screen

It is important to note that pop-ups are NOT modal – any visible items on the screen from which it was called can still be interacted with, though the pop-up will remain on the screen regardless.

Slide-in Screens

Slide-in screen configuration can also be found in the Screen Management section. They function similar to pop-up screens, but have a few distinct differences:

  1. There are only 4 slide-in screens, one from each direction. Each of them are global, so you cannot create as many as you want, unlike pop-ups.
  2. Slide-in screens do not need to be accessed by system function calls (although there is a system function if you prefer). Instead, if they are enabled, they may be accessed by pressing near the edge of the screen for which they are configured, and then clicking the handle. The visibility and functionality of the handle can be modified in the slide-in properties.


Click the handle on the side of the screen to access slide-in screens

Any normal control can be placed on a slide-in screen. In the above example, a static text is shown.

Summary

With the release of WinCC Comfort/Advanced V13 SP1, Siemens added several new features in addition to further stability and bug fixes. If you are still using V13 without the service pack, I highly recommend upgrading. Feel free to contact DMC with any questions or to get started on your next project.

Learn more about DMC's Siemens partnership and service offerings.

Comments

Jeff McCormick
# Jeff McCormick
Ahmed,

I'm afraid I don't have the project files anymore, but you can download one at http://openplclibrary.com/

The latest version includes an example project that uses pop-up screens in WinCC Comfort. The library also has a lot of other great things you can check out!

Ahmed Shehab
# Ahmed Shehab
would you mind to send the project files to create sample of it?

Post a comment

Name (required)

Email (required)

CAPTCHA image
Enter the code shown above: